Calculators / Box fill

Box fill calculator

Count the conductors, devices and wire connectors and check them against the box. Free, no sign-up.

Box

Box, trade size in inches

Insulated conductors in the box

Count every insulated conductor that enters the box. Leave out bare bonding wires and pigtails that never leave the box.

Devices and connectors

Only for a device deeper than 2.54 cm from the strap to the back, such as some GFCI receptacles and dimmers.

Need it on paper? SparkSheet™ saves your calculations under the job and prints them as a PDF with your logo, next to your job photos, panel schedules and plan markup.

Start 30 day free trial

How to use it

How box fill works

A box has to leave room for the conductors, the devices and the connectors in it, so the conductors are not crushed and the heat can get out. The Canadian Electrical Code gives each conductor size a space allowance, gives every listed box a usable volume, and counts the extras: a device takes the room of two conductors of the largest size connected to it, wire connectors take room in pairs, and a cable clamp or a fixture stud takes room too. A box with one conductor size can be checked by a simple count. A box with mixed sizes, or a box you measure yourself, is checked by adding the allowances and comparing them with the volume.

The calculator does both. It knows the common octagonal, square and device boxes, with their volumes, and takes a typed volume for anything else. The result says whether the box fits, how full it is, and the smallest listed box that takes the same contents.

Worked examples

A switch box with six #14 conductors

A 3 × 2 × 3 device box with six #14 conductors, one switch and two wire connectors. One conductor size in a listed box, so it is checked by count. The switch and the connectors take the room of three conductors, and the box allows seven, so the six conductors fit with one to spare.

The same box with eight conductors

Add a second cable and the count is eight #14 conductors against the same seven allowed. The box is too full. The calculator names the smallest listed box that takes the contents, which is the answer to carry to the supply house.

A junction box with mixed sizes

A 4 × 1-1/2 square box with four #14 and two #12 conductors, one device and four wire connectors. Mixed sizes, so it is worked out by space: the contents need 270.6 mL and the box has 344 mL, so it fits with room to spare.

Questions electricians ask

Do the bonding conductors count?

Insulated conductors count. Bare bonding conductors are treated differently under the rule, and the calculator asks for the insulated conductors that enter the box.

How does a receptacle count?

Each device takes the room of two conductors of the largest size connected to it, so a box with a device loses two from its allowed count, or the equivalent space.

Do wire connectors really take room?

Yes. The code counts them in pairs, each pair taking the room of one conductor, so a box full of splices fills faster than the conductor count suggests.

Why does a deep device change the method?

A dimmer or a smart switch that is deeper than a plain device needs more room than the two conductor allowance covers. The calculator switches to the space method and takes the device's depth into account.

What if my box is not in the list?

Choose Another box and type the volume marked inside it, in millilitres or cubic inches converted. The result is then worked out by space.

Does a conductor that passes straight through count?

Yes. A conductor that runs through the box without a splice still takes up room and is counted once.

Based on CEC 2024. Your province may have its own changes, so check them before you rely on a result. Checked by a Red Seal electrician at Peak Electrical Contracting, Victoria, BC.