Calculators / Voltage drop

Voltage drop calculator

Check a feeder or branch circuit against the CEC 3% and 5% limits. Free, no sign-up.

Your run

System
That current is
Conductor
Size
Power factor
Limit

Need it on paper? SparkSheet™ saves your calculations under the job and prints them as a PDF with your logo, next to your job photos, panel schedules and plan markup.

Start 30 day free trial

How to use it

What voltage drop is, and the limits the code uses

Every conductor has resistance, so some of the supply voltage is lost between the panel and the load. The longer the run and the smaller the conductor, the more is lost. The Canadian Electrical Code, in Rule 8-102, limits the drop to 3% on a feeder or a branch circuit and 5% in total from the service to the farthest outlet. A motor or a heater that sees too little voltage draws more current and runs hot, lights flicker, and electronics misbehave, so the limit is worth meeting even where an inspector never checks it.

The calculator works the drop from the conductor's resistance at 75 °C, the current, and twice the one way length. On larger conductors and motor loads, reactance matters too, so the power factor choice changes the answer. It handles 120 V and 240 V single phase, 347 V single phase, and 208 V and 600 V three phase.

Worked examples

A detached garage feeder

A 30 A feeder at 240 V to a garage 40 m from the panel. On #10 AWG copper the drop is 9.7 V, which is 4.03% and over the 3% limit. On #8 AWG copper it is 6.1 V, or 2.54%, and it passes. The calculator says #8 is the smallest conductor that meets the limit, so the feeder goes up one size for the distance even though #10 carries the current.

A hot tub circuit

A 40 A circuit at 240 V, 25 m one way, on #8 AWG copper. The drop is 5.1 V, or 2.12%, under the 3% limit, so the conductor sized for the current also meets the limit. Short runs rarely need an upsize.

A long 120 V branch circuit

A 20 A circuit loaded to 16 A, 30 m one way, on #12 AWG copper. The drop is 6.1 V, which is 5.10% of 120 V. Going to #10 brings it to 3.22%, still over 3%, and #8 is the first size that passes. A 120 V circuit loses twice the percentage of a 240 V circuit for the same current and distance, which is why long runs to a shed or a well pump are better at 240 V when the load allows it.

An aluminum service feeder

A 100 A feeder at 240 V, 50 m one way, on #1/0 AWG aluminum, checked against the 5% total limit. The drop is 6.5 V, or 2.72%, and it passes. Aluminum has higher resistance than copper for the same size, so an aluminum run is usually one or two sizes larger than the copper equivalent before it meets the limit.

Questions electricians ask

Is the 3% limit mandatory?

The code gives the limits in Rule 8-102, and provinces adopt the code with their own amendments. Treat 3% on a feeder or branch and 5% overall as the numbers to design to, and check your province's wording before relying on a result.

Does the length count both ways?

Enter the one way length. The current goes out and back, so the calculator uses twice the length in the calculation.

Why does the breaker size give a different answer than the load?

A breaker is sized above the load. Picking the breaker size uses 80% of its rating as the current, which is the continuous load the circuit is allowed to carry. The real connected load, when you know it, gives the exact drop.

When does power factor matter?

On motors and on larger conductors, where the conductor's reactance adds to the drop. For heaters, lighting and most receptacle loads, leave it at 100%.

Copper or aluminum?

The calculator does both. Aluminum needs a larger size for the same drop, and it is common on services and long feeders because it costs less per amp.

Does this size the conductor for current as well?

No. It checks the drop and finds the smallest size that meets the limit. The conductor still has to carry the current under the ampacity rules, and it has to suit the breaker. Use the larger of the two answers.

Based on CEC 2024. Your province may have its own changes, so check them before you rely on a result. Checked by a Red Seal electrician at Peak Electrical Contracting, Victoria, BC.