What it does
Single dwelling service and feeder calculation per CEC 2024 Rule 8-200(1): the itemized load of Subrule 1)(a) against the floor of 1)(b), the larger of the two in watts and amps, the next standard service size, and the minimum copper and aluminum service conductors at 75 °C from Tables 2 and 4. Tick the existing service to check it against the calculated load, and put the additions under Proposed added loads to get the new required service. The PDF prints the inputs, the steps and the result on one page for the permit. Suites, row housing and apartment buildings (8-200(2), 8-202) are in the SparkSheet™ app.
How the loads are counted
- Basic load, 8-200(1)(a)(i)(ii). 5,000 W for the first 90 m² of living area and 1,000 W for each further 90 m² or part of one. Living area per 8-110: the floors above grade in full and 75% of a finished basement with headroom over 1.8 m.
- Space heating and cooling, (a)(iii). Resistance heat per 62-118(3): the first 10 kW at 100% and the rest at 75%. A furnace, heat pump or air conditioner at 100%. Interlocked heating and cooling: the larger governs (8-106(3)). Not interlocked: both count.
- Range, (a)(iv). 6,000 W for a range up to 12 kW, plus 40% of the nameplate over 12 kW. A second range goes in at 25% under (vii).
- Tankless, pool, hot tub and spa heaters, (a)(v). 100%.
- EV supply equipment, (a)(vi). 100%, unless an EVEMS manages it: the managed load per 8-106(10), or left out per 8-106(11).
- Other loads over 1,500 W, (a)(vii). With an electric range, 25% of each. Without one, 100% of the first 6,000 W of their sum and 25% of the rest.
- The floor, 8-200(1)(b). 24,000 W where the floor area without the basement is 80 m² or more, 14,400 W below that.
The service is the next standard size at or above the calculated amps at 240 V (60, 100, 125, 150, 200, 320, 400 A). The conductors are the Table 2 and Table 4 minimums at 75 °C per 4-004 and 4-006. A utility may accept smaller dwelling service conductors under its own rules. Voltage drop is not included: there is a separate calculator for it.
Worked examples
Gas house, 2,000 ft², adding a 32 A EVSE
Range, 60 gallon tank, dryer. Basic 7,000 W, range 6,000 W, tank and dryer 9,500 W at 25% is 2,375 W: 15,375 W, under the 24,000 W floor, so 100 A. Add a 32 A charger at 7,680 W: 23,055 W, still under the floor. The existing 100 A service carries it. A 48 A charger pushes it past the floor.
All-electric, 1,800 ft² plus a 600 ft² finished basement, then a hot tub
Heat pump on a 40 A breaker with 3,000 W of supplementary baseboard, range, tank, dryer. Basic 7,000 W, heat 12,600 W (heat pump 9,600 plus baseboard 3,000, over the 9,600 W cooling side), range 6,000 W, other loads 2,375 W: 27,975 W, 116.6 A, 125 A service, #1 AWG copper or #2/0 AWG aluminum. A 40 A spa pack adds 9,600 W at 100%: 37,575 W, 156.6 A, 200 A service. On an existing 125 A service that is over by 32 A.
Small house, nothing electric but lights and plugs
1,200 ft², gas heat, gas range, gas water heater: 6,000 W. The floor still applies: 24,000 W, 100 A.
Questions electricians ask
Does an EV charger need a 200 A service?
Not by itself. On a gas-heated 100 A house a 24 A or 32 A charger usually fits under the floor, and an EVEMS keeps a larger one out of the calculation (8-106(11)). Run the numbers before quoting the upgrade.
Is the hot tub really at 100%?
Yes, 8-200(1)(a)(v). It is the load that most often forces the upgrade.
How does the finished basement count?
75% of its area, with a ceiling over 1.8 m (8-110). Unfinished space is left out.
Gas range: what changes?
No range allowance, and the other loads over 1,500 W go in at 100% of the first 6,000 W instead of 25% each (8-200(1)(a)(vii)(B)).
Why a 100 A minimum on a small house?
8-200(1)(b): 24,000 W at 80 m² and up. 60 A is only possible under 80 m², and most utilities and panels make 100 A the practical floor anyway.
Suites and multi-unit?
The app does house + suite, row housing and apartments with the 8-202(3) diversity ladder and the house panel.
Which edition?
CEC 2024, CSA C22.1:24. Check your province's amendments.
Is anything stored?
No. It runs in the browser and nothing is sent. The app saves calculations under the job.
Based on CEC 2024. Design aid, not a stamped document. Checked by a Red Seal electrician at Peak Electrical Contracting, Victoria, BC.