Calculators / Conduit fill

Conduit fill calculator

Mix conductor types and sizes in one run and find the smallest conduit that fits. Free, no sign-up.

Conduit

Type

Conductors in the run

Need it on paper? SparkSheet™ saves your calculations under the job and prints them as a PDF with your logo, next to your job photos, panel schedules and plan markup.

Start 30 day free trial

How to use it

How conduit fill works

The Canadian Electrical Code limits how much of a conduit's cross section the conductors may take up, so they can be pulled without damage and the heat they make can get out. The limit depends on how many conductors are in the run: one conductor may fill more of the space than two, and two more than three or more. The calculator takes the area of each conductor with its insulation, adds them up, and compares the total with the usable area of the conduit at the limit that applies.

It covers EMT, rigid PVC, rigid metal conduit, flexible metal conduit, liquid-tight flexible metal and non-metallic conduit, ENT and EB1 duct, with RW90, T90 and RWU90 conductors from #14 AWG up to the large kcmil sizes. The usable area differs by conduit type because the walls differ, so the same conductors can pass in one type and fail in another at the same trade size.

Worked examples

A mixed branch circuit run in EMT

Three #12 and two #8 T90 conductors in 21 mm (3/4") EMT. Five conductors, so the three or more limit applies. The conductors take 22.0% of the conduit, under the limit, and the run passes. The calculator also says 16 mm (1/2") would take this run, so the 21 mm is comfortable.

A sub-panel feeder in EMT

Four #6 T90 conductors in 27 mm (1") EMT fill 24.3% and pass. The smallest size that takes them is 21 mm (3/4"), but the larger conduit is often the better pull on a run with bends.

A service in rigid PVC

Four #3/0 RW90 conductors in 53 mm (2") PVC fill 33.7% and pass, and 53 mm is the smallest trade size that takes them. Going down a size would fail, so this is a run where the calculator earns its keep before the conduit is bought.

Questions electricians ask

Why does the limit change with the number of conductors?

One conductor can be pulled with more of the space filled because it does not bind against others. With three or more, the conductors jam against each other and need more free space to pull and to shed heat, so the limit is lower.

Does the bonding conductor count?

Yes. Every conductor in the conduit takes up area, including the bonding conductor, so add it as a line.

What about the 90 degree bends and the pull points?

Fill is one rule, and the number of bends between pull points is another. The calculator covers fill. Keep the bends within the rule's limit and add a pull box on a long run, and a conduit at the fill limit will still pull.

Can I put a cable in conduit?

A multi-conductor cable has its own rule based on its outside diameter, and this page does not cover it. It handles single conductors only.

Why is solid conductor a separate choice?

Solid and stranded conductors of the same size have slightly different outside diameters with the insulation on, so the area differs. The choice only applies to #14 to #10, where solid conductor is common.

Why does the same run pass in EMT and fail in flexible conduit?

The inside area of a trade size is not the same for every conduit type. Thicker walls leave less room, so the usable area, and the answer, change with the type.

Based on CEC 2024. Your province may have its own changes, so check them before you rely on a result. Checked by a Red Seal electrician at Peak Electrical Contracting, Victoria, BC.