What it does
Picks the smallest conductor that carries the load after every correction the code asks for, and names the limit that decided it. Copper from Table 2 (raceway or cable) or Table 1 (free air), aluminum from Tables 4 and 3, at the conductor's own insulation rating. Ambient above 30 °C takes the Table 5A factor for that rating. Four or more current-carrying conductors in a raceway or cable take Table 5C; two to four single conductors touching in free air take Table 5B, more than four fall back to the raceway table. The terminations get the same treatment under Rule 4-006: the value in the termination temperature column, corrected the same way, and the lower of the two is the ampacity you can use. A continuous load needs a conductor good for 125% of it on an 80% rated breaker (8-104(6)). The breaker is the next standard rating above the ampacity where the ampacity is not itself a standard rating (14-104(1)(a), Table 13), never more than 15, 20 and 30 A on No. 14, 12 and 10 copper or 15 and 25 A on No. 12 and 10 aluminum (14-104(2)).
Worked examples
A 40 A hot tub circuit, RW90 copper in conduit
The spa pack and its disconnect are not marked for 75 °C, so Rule 4-006 puts the terminations at 60 °C. No. 8 copper is 55 A in the 90 °C column but 40 A in the 60 °C column, and 40 A is what you get: No. 8 with a 40 A breaker. With 75 °C marked on both ends No. 8 is good for 50 A.
A 48 A EV charger, continuous
48 A continuous needs 60 A of conductor and breaker. No. 6 copper in the 60 °C column is 55 A, so unmarked equipment pushes you to No. 4. Mark the terminations 75 °C and No. 6 carries 65 A: No. 6 and a 60 A breaker. Check the charger's own instructions, since many name a minimum size.
A 100 A feeder through a 40 °C mechanical room
RW90 copper, 75 °C terminations. No. 3 is 115 A at 90 °C and 100 A at 75 °C; at 40 °C both take the 0.91 factor for a 90 °C conductor, so the termination side lands at 91 A and fails. No. 2 gives 104.65 A after the correction: No. 2 copper, protected at 110 A at most, 100 A here.
Five circuits sharing one conduit
Ten current-carrying conductors take the 0.7 factor from Table 5C. No. 12 copper at 60 °C terminations becomes 14 A, under a 20 A load, so the shared run goes to No. 10.
Questions electricians ask
Why does a 90 °C conductor only get the 60 °C number?
Rule 4-006. The breaker and the device the conductor lands on are rated for a termination temperature, and unmarked equipment rated 100 A or less is 60 °C. The insulation can run hotter, the lugs cannot. 75 °C marked on both ends unlocks the 75 °C column.
Does the neutral count as a current-carrying conductor?
Not when it carries only the unbalance of a balanced circuit (4-004(3)). It does count on a three-phase 4-wire system feeding line-to-neutral loads (4-004(4)). The bonding conductor never counts (4-004(6)).
Where does the 125% for a continuous load come from?
Rule 8-104(6): on an 80% rated breaker the continuous load may not exceed 80% of the conductor ampacity, which is the same as sizing for the load divided by 0.8. A breaker marked for 100% continuous operation drops that (8-104(5)).
Can the breaker be bigger than the ampacity?
Only when there is no device of that exact rating: the next standard rating in Table 13 is allowed up to 800 A (14-104(1)(a)). The small-conductor caps of 14-104(2) still apply.
NMD90 in a house?
A 90 °C conductor on 60 °C devices: No. 14 is 15 A, No. 12 is 20 A, No. 10 is 30 A, the same answers as always. The 90 °C column only helps where a correction factor eats into the ampacity and the terminations allow it.
What about voltage drop?
Not here. Size for ampacity first, then check the run on the voltage drop calculator and take the larger size.
Underground runs?
Sizes No. 1/0 and larger underground use the Diagram D8 to D11 tables or an IEEE 835 calculation (4-004(1)(d)). This page covers raceway, cable and free air runs; smaller underground conductors may use the raceway table (4-004(1)(f)).
Based on CEC 2024. Design aid, not a stamped document. Checked by a Red Seal electrician at Peak Electrical Contracting, Victoria, BC.