Calculators / Wire size

Wire size and ampacity calculator

The conductor for a load under CEC 2024 Tables 1 to 4, corrected for ambient, conductor count and terminations, with the breaker that goes with it. Free, no sign-up.

The load

The calculated load, or the breaker you are feeding. For a motor, enter 125% of the full load current.

Continuous, runs for an hour or more at a time

An EV charger, heat or a water heater is continuous.

The conductor

Material
Insulation rating
Where it runs
Current-carrying conductors together

Count the conductors in the raceway or cable that carry current. A neutral carrying only the unbalance and the bonding conductor do not count.

Where it ends up

Termination rating on the breaker and the equipment

Not marked: 60 °C for equipment rated 100 A or less, 75 °C above that.

Ambient temperature

Need it under the job? SparkSheet™ saves your calculations under the job and prints them as a PDF with your logo, next to your job photos, panel schedules and plan markup.

Start 30 day free trial

What it does

Picks the smallest conductor that carries the load after every correction the code asks for, and names the limit that decided it. Copper from Table 2 (raceway or cable) or Table 1 (free air), aluminum from Tables 4 and 3, at the conductor's own insulation rating. Ambient above 30 °C takes the Table 5A factor for that rating. Four or more current-carrying conductors in a raceway or cable take Table 5C; two to four single conductors touching in free air take Table 5B, more than four fall back to the raceway table. The terminations get the same treatment under Rule 4-006: the value in the termination temperature column, corrected the same way, and the lower of the two is the ampacity you can use. A continuous load needs a conductor good for 125% of it on an 80% rated breaker (8-104(6)). The breaker is the next standard rating above the ampacity where the ampacity is not itself a standard rating (14-104(1)(a), Table 13), never more than 15, 20 and 30 A on No. 14, 12 and 10 copper or 15 and 25 A on No. 12 and 10 aluminum (14-104(2)).

Worked examples

A 40 A hot tub circuit, RW90 copper in conduit

The spa pack and its disconnect are not marked for 75 °C, so Rule 4-006 puts the terminations at 60 °C. No. 8 copper is 55 A in the 90 °C column but 40 A in the 60 °C column, and 40 A is what you get: No. 8 with a 40 A breaker. With 75 °C marked on both ends No. 8 is good for 50 A.

A 48 A EV charger, continuous

48 A continuous needs 60 A of conductor and breaker. No. 6 copper in the 60 °C column is 55 A, so unmarked equipment pushes you to No. 4. Mark the terminations 75 °C and No. 6 carries 65 A: No. 6 and a 60 A breaker. Check the charger's own instructions, since many name a minimum size.

A 100 A feeder through a 40 °C mechanical room

RW90 copper, 75 °C terminations. No. 3 is 115 A at 90 °C and 100 A at 75 °C; at 40 °C both take the 0.91 factor for a 90 °C conductor, so the termination side lands at 91 A and fails. No. 2 gives 104.65 A after the correction: No. 2 copper, protected at 110 A at most, 100 A here.

Five circuits sharing one conduit

Ten current-carrying conductors take the 0.7 factor from Table 5C. No. 12 copper at 60 °C terminations becomes 14 A, under a 20 A load, so the shared run goes to No. 10.

Questions electricians ask

Why does a 90 °C conductor only get the 60 °C number?

Rule 4-006. The breaker and the device the conductor lands on are rated for a termination temperature, and unmarked equipment rated 100 A or less is 60 °C. The insulation can run hotter, the lugs cannot. 75 °C marked on both ends unlocks the 75 °C column.

Does the neutral count as a current-carrying conductor?

Not when it carries only the unbalance of a balanced circuit (4-004(3)). It does count on a three-phase 4-wire system feeding line-to-neutral loads (4-004(4)). The bonding conductor never counts (4-004(6)).

Where does the 125% for a continuous load come from?

Rule 8-104(6): on an 80% rated breaker the continuous load may not exceed 80% of the conductor ampacity, which is the same as sizing for the load divided by 0.8. A breaker marked for 100% continuous operation drops that (8-104(5)).

Can the breaker be bigger than the ampacity?

Only when there is no device of that exact rating: the next standard rating in Table 13 is allowed up to 800 A (14-104(1)(a)). The small-conductor caps of 14-104(2) still apply.

NMD90 in a house?

A 90 °C conductor on 60 °C devices: No. 14 is 15 A, No. 12 is 20 A, No. 10 is 30 A, the same answers as always. The 90 °C column only helps where a correction factor eats into the ampacity and the terminations allow it.

What about voltage drop?

Not here. Size for ampacity first, then check the run on the voltage drop calculator and take the larger size.

Underground runs?

Sizes No. 1/0 and larger underground use the Diagram D8 to D11 tables or an IEEE 835 calculation (4-004(1)(d)). This page covers raceway, cable and free air runs; smaller underground conductors may use the raceway table (4-004(1)(f)).

Based on CEC 2024. Design aid, not a stamped document. Checked by a Red Seal electrician at Peak Electrical Contracting, Victoria, BC.